in place to make certain that the red wire cannot contact any
metal parts or the electrical box.
When alarms are interconnected, all interconnected units must
be powered from a single circuit.
A maximum of 24 Kidde/Lifesaver devices may be intercon-
nected in a multiple station arrangement. The interconnect sys-
tem should not exceed the NFPA interconnect limit of 12 smoke
alarms and/or 18 alarms total (smoke, heat, carbon monoxide,
etc.). With 18 alarms interconnected, it is still possible to inter-
connect up to a total of 6 remote signaling devices and/or relay
modules.
When mixing models which have battery backup (Kidde mod-
els: 1275, 1276, 1285, 1296, i12040, i12060, i12080, i4618,
PE120, PI2000, PI2010, RF-SM-ACDC, KN-SM-FM-I, KN-COSM-
IB, HD135F, KN-COB-IC, KN-COP-IC, KN-COPF-I and FireX
models: AD, ADC, FADC) with models without battery backup,
(Kidde models: 1235, i12020, KN-COSM-I, 120X, SM120X,
CO120X, SL177) be advised that the models without battery
backup will not respond during an AC power failure.
The maximum wire run distance between the first and last unit
in an interconnected system is 1000 feet.
Figure 4 illustrates interconnection wiring. Improper connection
will result in damage to the alarm, failure to operate, or a shock
hazard.
Make certain alarms are wired to a continuous (non-switched)
power line. NOTE: Use standard UL listed household wire (as
required by local codes) available at all electrical supply stores
and most hardware stores.
FIGURE 4 INTERCONNECT WIRING DIAGRAM
WIRES ON ALARM HARNESS CONNECTED TO
1475-7205-00(820-0905-EN).indd 61475-7205-00(820-0905-EN).indd 6 2009.11.27 2:00:43 PM2009.11.27 2:00:43 PM